IDPT 数显式微差压变送器

本产品适用于暖通空调(HVAC)、能源 管理系统、VAV及风扇控制、环境污染控制静 态管路和洁净室压力、烟雾罩控制、烘箱增 压及炉通风控制等领域。

| A量程 | B显示屏 | C输出方式 | D精度 |
| 0=-1000~1000Pa | 0=有显示屏 | A=4~20mA,0-5/10VDC | ±1.0%FS |
| 2=-10000~10000Pa | N=无显示屏 | B=4~20mA(两线制) |
| 6=-100~100Pa | C=0~10VDC(三线制) | ||
| D=0~5VDC(三线制) |
技术参数
| 常规 | 数值 |
精度 | ±1.0%FS |
压力单位 | Pa,mmH2O,mbar,inWG,mmHG,daPa,hPa(其它单位可选) |
输出信号 | 0~5/10VDC和4~20mA(两组同时输出),4~20mA(二线制),0~5/10VDC(三线制) |
电源供应 | 两组同时输出时,输入电压为16~30VDC/VAC,并可配220VAC24VDC适配器供电 (接头规格为3.5×1.35)4~20mA(二线制)输出时,输入电压为无极性的16~30VDC;0~5VDC 三线制)、0~10 VDC(三线制)输出时,输入电压为16~30VDC |
| 功耗 | 1.5W左右 |
| 响应时间 | 20ms,0.5s,1s,2s |
分辨率 | IDPT 110:1Pa,1mmH2O,0.01mbar,0.04inWG,0.007mmHG,0.1daPa,0.001kPa |
| IDPT 112:0.01hPa | |
| IDPT 116:0.1Pa,0.01mmH2O,0.001mbar,0.01daPa,0.001hPa |
| 零点校准 | 手动按键零点校准 |
| 测量介质 | 空气和中性气体 |
| 工作温度 | -10~60℃ |
| 存储温度 | -10~70℃ |
允许过压 | 量程 过载能力 |
| -1000~1000Pa -15000~15000Pa | |
-10000~10000P -150000~150000Pa | |
| -100~100Pa -4500~4500Pa |
产品操作说明

IDPT 微差压传感器/变送器

产品特色
IDPT 系列微差压传感器/变送器是检测差压或表压压力,并把 这个压力值转换为成比例的电信号输出,用于智能楼宇能源管理 系统,起到测量楼宇增压和空气流动控制所需的精确压力和流 量。
使用压力值可以通过IDPT 系列产品内置的拨码开关进行现场设 定。
量程:0 ~ ±10Pa/0 ~ ±10,000Pa
精度:±1.0% • 多种压力单位可切换
LCD背光数字显示屏或无显示屏
开机自动零点校准
响应时间通过产品内置的拔码开关现场可调(0.5S ~4S)
手动按键压差零点校准
采用进口微压芯体
旋转方式固定于安装背板(安装板与主机分体,这样可以实行 分步分期式安装)
技术规格
量程 | IDPT 110 -1,000 ~ +1,000Pa 最小可设0~+100Pa IDPT 112 -10,000 ~ +10,000Pa 最小可设0~+1000Pa IDPT 116 -100 ~ +100Pa 最小可设0~+10Pa |
精确度 | ±1.0% |
| 压力 单位 | Pa,mmH O,mbar,inWC,mmHG,daPa,KPa,hPa |
输出信号 | 0~5VDC、0~10VDC、4~20mA、RS-485信号 (二线制、三线制输出,可同时使用模拟信号;RS-485型只 有RS-485信号输出) |
电源供应 | 两组同时输出,输入电压为16~30VAC/VDC,可配24VDC适配 器(3.5x1.35mm)供电 ①4~20mA (两线制)输出,输入电压为无极性 的12~30VDC 0~5V/10VDC输出,输入电压16~30VAC/VDC RS-485输出,输入电压为12~30VAC/VDC |
| 功耗 | ≤1.5W |
| ① 无极性:输入电压源不分正负极 |
选型表

变送器功能
| 响应时间 | 0.5s,1s,2s,4s |
分辨率 | IDPT 110 1Pa,0.1mmH O,0.01mbar,0.004inWG, IDPT 112 0.007mmHG,0.1daPa,0.001KPa,0.001hPa IDPT 116 0.1Pa,0.01mmH O,0.01mbar,0.01daPa,0.001hPa |
| 零点校准 | 手动按键零点校准 |
| 测量介质 | 空气和中性气体 |
| 允许过压 | 15KPa(IDPT 110);150KPa(IDPT 112);4.5KPa(IDPT 116) |
| 使用温度 | -10~60+℃ |
| 存储温度 | -10~+70℃ |
机械参数
外壳材质:工业塑料,防护等级IP54
显 示 屏:背光液晶显示,50×22.5 mm(二线制无背光)
数字高度:测量值 10 mm,单位 5 mm
压力接口:金属倒刺接口,Ø 6.2 mm
电缆接头:电缆最大直径Ø 8 mm
重 量:166g

功能详解





一、显示功能
显示压力值,同时可切换显示单位Pa、mmH O、inWG、 2 mmHG、daPa、KPa、hPa、mbar。
二、设置功能
通过面板背面(显示面为正面)设置按钮进行精度校准。 以量程-1,000~1,000Pa为例,按按钮进入校准界面,将压力源调 至-1,000Pa,继续按键保存当前值为-1,000Pa,之后每增加 500Pa进行一次校验。若校准时前一个值大于等于后一个值,则 校验失败显示“Err”,校验值不保存。(需在高精度压力源下进 行校验,用户请勿轻易使用)
三、手动清零
按面板背面(显示面为正)按钮可进行手动清零,零点将 被保存。(如果客户现场安装时发现通电后液晶显示压力值或 输出信号有偏差时,请保持与安装方式平行的状态下手动清 零)
四、拨码开关设置
①量程设置 量程拨码开关上三位进行量程设定(量程只关乎输出,举 例:置量程100Pa即显示0~100Pa时对应模拟量输出4~20mA和 0~5VDC /0~10VDC)。
量程拨码 开关组合 | 单位/型号 | Pa | mmH O 2 | mbar | inWG | mmHG | daPa | KPa | hPa |
| IDPT 116 | 10.0 | 1.00 | 0.100 | / | / | 1.00 | / | 0.100 |
| IDPT 110 | 100 | 10.0 | 1.00 | 0.40 | 0.75 | 10.0 | 0.100 | 1.00 | |
| IDPT 112 | 1,000 | 100.0 | 10.00 | 4.00 | 7.50 | 100 | 1.000 | 10.00 |
![]() | IDPT 116 | 25.0 | 2.50 | 0.250 | / | / | 2.50 | / | 0.250 |
| IDPT 110 | 250 | 25.0 | 2.50 | 1.00 | 1.87 | 25.0 | 0.250 | 2.50 | |
| IDPT 112 | 2,500 | 250.0 | 25.00 | 10.00 | 18.75 | 250.0 | 2.500 | 25.00 |
![]() | IDPT 116 | 50.0 | 5.00 | 0.500 | / | / | 5.00 | / | 0.500 |
| IDPT 110 | 500 | 50.0 | 5.00 | 2.00 | 3.750 | 50.0 | 0.500 | 5.00 | |
| IDPT 112 | 5,000 | 500.0 | 50.00 | 20.00 | 37.50 | 500.0 | 5.000 | 50.00 |
![]() | IDPT 116 | 75.0 | 7.50 | 0.750 | / | / | 7.50 | / | 0.750 |
| IDPT 110 | 750 | 75.0 | 7.50 | 3.00 | 5.62 | 75.0 | 0.750 | 7.50 | |
| IDPT 112 | 7,500 | 750.0 | 75.00 | 30.00 | 56.20 | 750.0 | 7.500 | 75.00 |
![]() | IDPT 116 | 100.0 | 10.00 | 1.000 | / | / | 10.00 | / | 1.000 |
| IDPT 110 | 1,000 | 100.0 | 10.0 | 4.00 | 7.50 | 100.0 | 1.000 | 10.00 | |
| IDPT 112 | 10,000 | 1,000.0 | 100.00 | 40.00 | 75.00 | 1,000.0 | 10.000 | 100.00 |
全量程/量程置中设置(0~1,000Pa为例)若需要设置量程种 类,将量程拨码开关最下一位依照下图提示设置于对应的位置即 可。

⚠请小心地依照拨码开关的组合设置变送器。变送器开启电 源后, 如果显示屏出现 “Err”, 表示拨码开关设置错误。如发生 上述情况时, 先关闭变送器电源, 重新设置正确的拨码开关组合, 然后再重新启动电源即可。
②单位设置
单位拨码开关上三位测量单位设置:请依照下图将拨码开关 拨到相应位置
设置 种类 | Pa | mmH2 O | mbar | inWG |
拨指 开关 位置 | ![]() | ![]() | ![]() | ![]() |
设置 种类 | mmHG | daPa | KPa | hPa |
| 拨指 开关 位置 | ![]() | ![]() | ![]() | ![]() |
③自动清零设置
单位拨码开关最下面一位为开机自动置零(开机自动置零数 据不保存,即当自动置零关闭时,零点位置恢复致最后一次标 定值)。

④响应时间设置
响应时间拨码开关设置响应时间:请依照下图将拨码开关拨到 相应位置
设置 种类 | 0.5s | 1s | 2s | 4s |
拨指 开关 位置 | ![]() | ![]() | ![]() | ![]() |
⑤通讯模式设置
响应时间拨码开关设置RS-485通讯模式:请依照下图将拨码开 关拨到相应位置。(只适用于RS-485通讯款)

图4排针为RS-485 A-B线匹配电阻跳线,当通讯距离超过300米 时,可选择将末端仪表跳线连接,以降低通讯电路信号反射干扰。
电器接线


备注:取下前盖堵头和后盖橡胶塞,将导线穿过防水接头,正确 接入端子,旋紧防水接头、盖好后盖橡胶塞即可。
安装方式
将塑料背板固定在墙面。(钻孔Ø6mm,深度30mm,随货提供 螺丝和配件)将变送器置于背板上(请见右图中的A部位)顺时 针旋转变送器,当听到卡入声即是正确的安装变送器。

维修保养
请避免使用刺激性溶剂或使用含有甲醛(福尔马林)成分的 清洁剂清洁变送器和探头。
选购和配件
源适配器
连接用软管
常见问题及解决办法
1、显示量程或单位与设置不符。
① 拨码开关未拨到位,下电重拨后重新启动
2、加压后压力显示或输出值无变化(多显示为0或者 FULL)或变化不准。
① 加载压力是否超过爆破压力直接冲坏压力芯体;
② 使用介质是否存在腐蚀性或者与所购产品适用介质存 在出入(现有微压差变送器均为无腐蚀性气体);
③ 检查进气软管有无异物阻塞(颗粒物或者水柱)或泄 漏;
④ 使用环境温度是否超出补偿温度范围(微压差变送器 温度补偿范围-10~60℃);
⑤ 有无在加压情况下进行清零误操作,如有则在确定无 输入压力状态下再次清零;
⑥ 有无对设置按钮进行误操作(设置按钮有防误操作机 制,即设置点压力值必须从小往大递增才能最后设置成功,需 在高精压力源下进行校准设置,不推荐客户自行校准,如因校 准操作造成偏差,则需返厂重校)。
3、压力显示值正常,无输出模拟量或模拟量输出不 准。
① 检查输出线连接是否正常;
② 三线制输出则需检测变送器与控制仪表共地是否正常 (即地线必须相连);
③ 检查负载电阻选用是否恰当。
4、零点压力值有轻微漂移。
① 待漂移稳定后进行清零操作。
如上述方法无法消除故障,则与厂家联系!